AC drive,frequency inverter, frequency converter......

KET 3000W

Control Signal Wiring Diagram

Control Signal WIring Diagram

Model of KET-3000W series inverter

KET-3000W Model Rated Capacity(KVA) Rated Input Current (A) Rated Output Current (A) Adaptable Motor Power (KW) Rated Input Voltage(V)
0R2S2 0.6 4.3 1.7 0.25 220~240
0R4S2 1.0 5.8 2.5 0.4
0R7S2 1.5 10.5 4.0 0.75
1R5S2 2.8 18.5 7.5 1.5
2R2S2 3.8 24.1 10.0 2.2
0R4T4 1.0 1.8 1.4 0.4 380~440
0R7T4 1.5 3.4 2.3 0.75
1R5T4 2.5 5.2 3.8 1.5
2R2T4 3.4 7.3 5.1 2.2
3R7T4 5.9 11.9 9.0 3.7
5R5T4 8.5 15 13 5.5
7R5T4 11 19 17 7.5
011T4 16 28 25 11
015T4 21 35 32 15
018T4 24 39 37 18.5
022T4 30 47 45 22
030T4 39 62 60 30
037T4 49 77 75 37
045T4 59 92 90 45
055T4 72 113 110 55
075T4 100 156 152 75
090T4 116 180 176 90
110T4 138 214 210 110
132T4 167 256 253 132
160T4 200 307 304 160
200T4 250 385 380 200
220T4 280 430 426 220
250T4 309 475 470 250
280T4 349 535 530 280
315T4 398 609 600 315
355T4 434 664 660 355
400T4 494 754 750 400


Standard  Specification :

Item
Specification
input Rated voltage, frequency Single phase,220V,50Hz/60Hz; 3 phase, 380V,50Hz/60Hz
Allowed fluctuation Continuous voltage fluctuation:within±10%, instant voltage fluctuation: within -15%10%; voltage imbalance: <3%; frequency fluctuation: within 5%.
output Voltage Single phase,0-220V; 3 phase,0-380V
Output frequency 0-400Hz.
Overload capability 150% rated current,2 minutes; 180% rated current,10 seconds
control trait Command input mode By LCD keypad, by terminals, by PC through serial communication port.
Control mode Open loop vector control, VF control.
Speed setting method By keypad, by analog, by PC through serial communication port
Speed setting precision Digital command±0.01%(-10 +40)
analog command±0.1%(25oC±10)
Speed setting resolution Digital command:0.01Hz; analog command:1/2000 of maximum frequency
Speed control precision Open loop vector control: ±0.5%; (25±10
Speed control range Open loop vector control: 1:100
Torque control response Open loop vector control : <200ms.
Start torque Open loop vector control: 150% of rated torque at 0.5Hz.
Torque control precision ±5%
  Set reference voltage supply output 1 port, +10V, 5mA
Control voltage supply output 24V,100mA
Analogy input 2 ports, AI1 voltage: 010V, AI2 current/optional voltage010V/020mA AC.
Analog meter output 2 ports,0-10V/0-20mA DC, current/voltage optional
Operation command connector input 2 ports, FWD: forward operation, REV: reverse operation
Programmable connector input X1X8, 8 ports, programmable digital signal input terminals, X7 and X8 can accept high-speed pulse signal(3.7KW or below, X1X5, 5 ports, X4 and X5 are high speed input)
DO frequency signal output 1 port, high-frequency signal output(programmable)
Collector open-loop output Two ports:Y1, Y2.   Y2 can be selected as pulse output(3.7KW or below, only Y1 available)
Programmable relay output 1 port RA/RB/RC, contactor capacity: 250V AC/3A or 30V DC/1A
Serial communication port RS-485 connector RS485+,RS485-
4 bits LED display setting frequency, output frequency, output voltage, output current, motor speed, output torque, switch value terminal, programming menu parameters and fault code.
Five indication lamp Parameter unit, RUN/STOP status, special status, charging status.
Protection function Protection function Over voltage, under voltage, current limitation, over current, overload of inverter, overload of motor, overheat, overvoltage stallout, load short circuit, phase fault.
  Protection degree IP20
Cooling mode Forced air cooling
envirenment Ambient termearture -10,+40
Termperature 2090% RH(no condensation)

Storage termperature

-20,+70

Application area

indoor(no corrosive odor, dust)

Installation area

Altitude is not more than 1000meter, no dust, no corrosive order, no direct sunlight.

Vibration

20Hz less than 9.8m/s2(0.2g)

 

Features:

  • Open-loop vector control
  • Built-in PLC
  • Built-in PID regulator
  • 16-step speed
  • traverse operation
  • Continuous operation function at momentary power failure
  • Perfect fault protection and auto current limit
  • Positive/negative logic switch input signal for option 
  • 43 input terminals and 25 output terminals for option
  • 10 frequency input modes
  • RS-485 communication port (MODBUS protocol)
  • Autotuning function in the mode of either standby or operation